Aerodynamics of Buildings and Structures

Four interactive models for Chapter 5. Move the sliders and watch the results change.

Power law U(z) = U₁₀ (z/10)α. Rougher terrain slows the wind near the ground and has a larger exponent α and higher turbulence intensity Iu. The same U₁₀ is used for every terrain so the shapes can be compared.

q = ½ρU² with ρ = 1.2 kg/m³. Net load Δp = (Cpe − Cpi) q. Windward wall Cp = +0.7 and leeward wall Cp = −0.4 are typical mean values. Raise Cpi to +0.7 (a windward door blown open) and watch the roof uplift almost double.

St = fD/U, so the shedding frequency is f = St·U/D. Resonance happens when f approaches fn, at the critical speed Ucr = fnD/St. The vortices drawn alternate at a slowed-down rate.

Openings in series: 1/Aeff² = 1/A₁² + 1/A₂². Wind: Qw = Cd Aeff U √ΔCp. Stack: Qs = Cd Aeff √(2ghΔT/T). Combined: Q ≈ √(Qw² + Qs²), with Cd = 0.6 and T = 293 K. A sheltered building has a smaller ΔCp, so try lowering it.